®
RIM100
Run Indicator Module
User’s Manual
Revision 1.0
Copyright © 2008 Maretron, LLP All Rights Reserved
Maretron, LLP
9014 N. 23rd Ave #10
Phoenix, AZ 85021-7850
Maretron Manual Part #: M002001
Revision 1.0
Page i
®
Table of Contents
1 Introduction ...........................................................................................................................1
1.1 Firmware Revision.................................................................................................... 1
1.2 RIM100 Features...................................................................................................... 1
1.3 Quick Install.............................................................................................................. 1
2 Installation.............................................................................................................................2
2.1 Unpacking the Box ................................................................................................... 2
2.2 Choosing a Mounting Location................................................................................. 2
2.3 Mounting the RIM100 ............................................................................................... 3
2.4 Connecting the RIM100............................................................................................ 3
2.4.1 NMEA 2000® Connection............................................................................... 3
2.4.2 Monitored Load Connections......................................................................... 4
2.4.2.1 AC Load........................................................................................... 5
2.4.2.2 DC Load........................................................................................... 5
2.4.3 Checking Connections................................................................................... 6
2.5 Configuring the RIM100............................................................................................ 6
2.5.1 Device Instance ............................................................................................. 6
2.5.2 Channel #1 - #6 Mode ................................................................................... 7
2.5.3 Channel #1 - #6 Label ................................................................................... 7
2.5.4 Advanced Configuration…............................................................................. 7
2.5.5 NMEA 2000® PGN Enable/Disable................................................................ 7
2.5.6 Restore Factory Defaults............................................................................... 7
2.5.7 Installation Description…............................................................................... 7
4 Troubleshooting ....................................................................................................................8
5 Technical Specifications........................................................................................................9
6 Technical Support ...............................................................................................................10
7 Installation Template ...........................................................................................................11
8 Maretron (2 Year) Limited Warranty....................................................................................12
Table of Figures
Figure 2 – NMEA 2000® Connector Face Views ....................................................................... 4
Figure 3 – AC Load Connection Diagram.................................................................................. 5
Table of Appendices
Appendix A – NMEA 2000® Interfacing.................................................................................... A1
Revision 1.0
Page iii
®
1 Introduction
Congratulations on your purchase of the Maretron Run Indicator Module (RIM100). Maretron
has designed and built your RIM100 to the highest standards for years of dependable and
accurate service.
Maretron’s RIM100 monitors both AC and DC electrical circuits and reports, over an NMEA
2000® network, whether or not the electrical circuit is energized and running. The RIM100
works equally as well for monitoring manually switched loads (e.g., running lights, anchor
lights, or deck lights) as it does for automatically switched loads. Monitoring automatically
switched loads (e.g., bilge pumps, engine exhaust/intake fans, and transfer pumps) via the
RIM100 is especially useful because you know exactly when equipment is, or isn't running.
The Maretron RIM100 is designed to operate within the harsh demands of the marine
environment. However, no piece of marine electronic equipment can function properly unless
installed, configured, and maintained in the correct manner. Please read carefully and follow
these instructions for installation, configuration, and usage of the Maretron RIM100 in order to
ensure optimal performance.
1.1 Firmware Revision
This manual corresponds to RIM100 firmware revision 1.0.2.
1.2 RIM100 Features
The Maretron RIM100 has the following features.
• NMEA 2000® Interface
• Waterproof Connectors
• Sealed Waterproof Enclosure
• Opto-Isolated from NMEA 2000® Eliminating Potential Ground Loops
•
Monitors and reports the running status of connected devices
• Works with both AC and DC loads
• Works with both automatically and manually switched loads
• Can indicate the status of a wide variety of loads
o Bilge Pumps
o Winches
o Running Lights
o Transfer Pumps
o Exhaust/Intake Fans
1.3 Quick Install
Installing the Maretron RIM100 involves the following five steps. Please refer to the individual
sections for additional details.
Revision 1.0
Page 1
RIM100 User's Manual
2 Installation
2.1 Unpacking the Box
When unpacking the box containing the Maretron RIM100, you should find the following items:
1 – RIM100 – Run Indicator Module
1 – Parts Bag containing 4 Stainless Steel Mounting Screws
1 – RIM100 User’s Manual
1 – Warranty Registration Card
If any of these items are missing or damaged, please contact Maretron.
2.2 Choosing a Mounting Location
Please consider the following when choosing a mounting location.
1. The RIM100 is waterproof, so it can be mounted in a damp or dry location.
2. The orientation is not important, so the RIM100 can be mounted on a horizontal deck,
vertical bulkhead, or upside down if desired.
3. The RIM100 is temperature-rated to 55°C (130°F), so it should be mounted away from
engines or engine rooms where the operating temperature exceeds the specified limit.
Page 2
Revision 1.0
®
2.3 Mounting the RIM100
Attach the RIM100 securely to the vessel using the included stainless steel mounting screws
Figure 1 – Mounting the RIM100
2.4 Connecting the RIM100
The RIM100 requires two types of electrical connections: 1) the NMEA 2000® connection (refer
2.4.1 NMEA 2000® Connection
The NMEA 2000® connector can be found on the side of the enclosure. The NMEA 2000®
NMEA 2000® network using a Maretron NMEA 2000® cable (or compatible cable) by
connecting the female end of the cable to the RIM100 (note the key on the male connector and
keyway on the female connector). Be sure the cable is connected securely and that the collar
on the cable connector is tightened firmly. Connect the other end of the cable (male) to the
NMEA 2000® network in the same manner. The RIM100 is designed such that you can plug or
unplug it from an NMEA 2000® network while the power to the network is connected or
disconnected. Please follow recommended practices for installing NMEA 2000® network
products.
Revision 1.0
Page 3
RIM100 User's Manual
Figure 2 – NMEA 2000® Connector Face Views
2.4.2 Monitored Load Connections
The RIM100 monitored load connections are made by connecting to the 12-pin terminal strip
on the top of the unit. First, remove the four screws at the corners of the unit detaching the
splash guard from the unit. On the bottom of the splash guard, you will find a label detailing
the wire connection to pin number assignments, which are repeated in the table below.
Pin #
1
Signal Name
V1+
Connection
Voltage #1 (+ for DC monitored loads)
Voltage #1 (- for DC monitored loads)
Voltage #2 (+ for DC monitored loads)
Voltage #2 (- for DC monitored loads)
Voltage #3 (+ for DC monitored loads)
Voltage #3 (- for DC monitored loads)
Voltage #4 (+ for DC monitored loads)
Voltage #4 (- for DC monitored loads)
Voltage #5 (+ for DC monitored loads)
Voltage #5 (- for DC monitored loads)
Voltage #6 (+ for DC monitored loads)
Voltage #6 (- for DC monitored loads)
2
3
4
5
6
7
8
9
V1-
V2+
V2-
V3+
V3-
V4+
V4-
V5+
10
11
12
V5-
V6+
V6-
The RIM100 will detect the presence or absence of either AC or DC voltages. Before
attempting to connect the RIM100 to the AC source, determine the type of system you will be
monitoring. The RIM100 supports the connection and monitoring of two different system types;
Page 4
Revision 1.0
®
WARNING: The voltages present on AC circuits can cause electrocution.
Before making any electrical connections to the RIM100, ensure that power is
removed from all AC circuits that will be connected to the RIM100. Only restore
AC power after all connections have been made to the RIM100 and the splash
guard has been re-installed.
WARNING: User supplied voltage sense cables must be 18 gauge or larger,
have insulation rated to 600V, and must have the conductor connected to the
hot lead of the AC power source protected by a fuse rated at 3A or less (the
current consumed by the voltage sense circuit on the RIM100 is negligible, at
less than 10mA).
2.4.2.1 AC Load
terminal from the load to either terminal of the pair of terminals on the RIM100. This figure
shows the connection of the monitored load to channel 1 via the terminals named V1+ and
V1-. Connections to other channels are similar.
User-Supplied Components
Power Switch
Fuse
To AC Breaker
Panel
Monitored
AC Load
Fuse
RIM100 Screw Terminals
1
2
3
4
5
6
7
8
9 10 11 12
Figure 3 – AC Load Connection Diagram
2.4.2.2 DC Load
you must connect the positive voltage from the monitored load to the terminal marked “+” and
the negative voltage from the monitored load to the terminal marked “-”. This figure shows the
connection of the monitored load to channel 1 via the terminals named V1+ and V1-.
Connections to other channels are similar.
Revision 1.0
Page 5
RIM100 User's Manual
User-Supplied Components
Power Switch
Fuse
+ To DC
- Breaker Panel
Monitored
DC Load
Fuse
RIM100 Screw Terminals
1
2
3
4
5
6
7
8
9 10 11 12
Figure 4 – DC Load Connection Diagram
2.4.3 Checking Connections
Once the NMEA 2000® connection and load connection(s) to the RIM100 have been
completed, check to see that information is being properly transmitted by observing an
“Troubleshooting”.
2.5 Configuring the RIM100
The RIM100 will transmit data over the NMEA 2000® network as it is shipped from the factory;
however, it may require configuration, depending on how many loads are being monitored.
There are several configurable items within the RIM100, which are detailed in the remainder of
this section.
You configure the RIM100 using a Maretron DSM250 display or other NMEA 2000® display
unit that is capable of configuring the RIM100. Please refer to the Maretron DSM250 User’s
Manual for details.
2.5.1 Device Instance
NMEA 2000® provides a unique device instance for each switch/run monitoring device on a
vessel. This value should be programmed in each RIM100 so that each RIM100 is associated
with a unique device instance number. The default instance number is 0, which is used to
indicate the first RIM100 that is hooked to the network. Subsequent RIM100s connected to the
network would be numbered 1, 2, and so on.
Page 6
Revision 1.0
®
2.5.2 Channel #1 - #6 Mode
You must configure the RIM100 as to whether a particular channel should be enabled. The
allowable values for this parameter are as follows:
• “Enable” (default) – Use this value if the channel is being used to monitor a load.
• “Disable” – Use this value if no load circuit is connected to the corresponding channel’s
terminals. The RIM100 will indicate that no data is available for this circuit.
2.5.3 Channel #1 - #6 Label
Each channel that can be monitored by the RIM100 may be programmed with a text label that
will be displayed in monitoring software and displays that recognize device labels, such as the
Maretron N2KView Vessel Monitoring System and the Maretron DSM250 display. The label
will let you assign an easy-to-remember text label (example: “Forward Bilge Pump”) to make it
easy for you to identify the device being monitored.
2.5.4 Advanced Configuration…
Certain parameters do not normally need to be set in order for normal operation, but are
included in an advanced configuration section for use in special situations.
2.5.5 NMEA 2000® PGN Enable/Disable
The RIM100 is capable of transmitting NMEA 2000® messages (or PGNs) associated with
monitored load circuits. You may individually enable or disable each of these messages. You
may also change the rate of transmission of each of these messages if desired.
2.5.6 Restore Factory Defaults
Selecting this configuration option causes all stored parameters in the RIM100 to be reset to
the values they contained when the unit was manufactured.
2.5.7 Installation Description…
The RIM100, along with all other Level A certified NMEA devices, has two user-programmable
installation description fields. You may program these fields with information specific to the
device, such as date installed, the initials/name of the installer, the physical location of the
device, etc. This configuration option will allow you to program the values of these fields.
3 Maintenance
Regular maintenance is important to ensure continued proper operation of the Maretron
RIM100. Perform the following tasks periodically:
• Clean the unit with a soft cloth. Do not use chemical cleaners as they may remove
paint or markings or may corrode the RIM100 enclosure or seals.
• Ensure that the unit is mounted securely and cannot be moved relative to the mounting
surface. If the unit is loose, tighten the mounting screws.
Revision 1.0
Page 7
RIM100 User's Manual
• Check the security of the cable connected to the NMEA 2000® connector, and tighten if
necessary.
• Check the security of all of the load connections on the top of the unit and tighten if
necessary.
4 Troubleshooting
If you notice unexpected operation of the Maretron RIM100, follow the troubleshooting
procedures in this section to remedy simple problems. If these steps do not solve your
information).
Symptom
Troubleshooting Procedure
No Run Indicator data
visible on NMEA 2000®
network.
Ensure that the RIM100 is properly connected to the NMEA 2000®
network.
Ensure that the monitored loads are properly connected to the
RIM100.
Ensure that each indicator that you wish to monitor is not
configured as “Disabled”.
Ensure that the RIM100 has the appropriate NMEA 2000® PGNs
A Run Indicator always
reads “Off”
Ensure that there is not an open circuit in the wiring for the load.
With the load running, measure the voltage between the “+” and “-”
terminals on the RIM100 to which the load is connected. You
should measure an appropriate AC or DC voltage, depending upon
the type of load.
Page 8
Revision 1.0
®
5 Technical Specifications
As Maretron is constantly improving its products, all specifications are subject to change
without notice. Maretron products are designed to be accurate and reliable; however, they
should be used only as aids to navigation and not as a replacement for traditional navigation
aids and techniques.
Specifications
Parameter
“ON” Voltage Range (DC)
“ON” Voltage Range (AC)
Value
9VDC to 240VDC
9VAC to 240VAC
Comment
RMS
Certifications
Parameter
Comment
NMEA 2000® Standard
Level A
Maritime Navigation and Radiocommunication Equipment & Systems
Maritime Navigation and Radiocommunication Equipment & Systems
FCC and CE Mark
IEC 61162-3
IEC 60945
Electromagnetic Compatibility
NMEA 2000® Parameter Group Numbers (PGNs)
Description
PGN #
PGN Name
Default Rate
Periodic Data PGNs
127501 Binary Switch Bank Status
1 time/15 seconds and on
switch change
Response to Requested
PGNs
126464 PGN List (Transmit and Receive)
126996 Product Information
126998 Configuration Information
059392 ISO Acknowledge
059904 ISO Request
060928 ISO Address Claim
065240 ISO Address Command
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Protocol PGNs
126208 NMEA Request/Command/Acknowledge
126720 Configuration
N/A
N/A
Maretron Proprietary PGNs
Electrical
Parameter
Value
Comment
Operating Voltage
9 to 32 Volts
DC Voltage
Power Consumption
Load Equivalence Number (LEN)
Reverse Battery Protection
Load Dump Protection
50 mA
1
Yes
Yes
NMEA 2000® Interface
NMEA 2000® Spec. (1LEN = 50 mA)
Indefinitely
Energy Rated per SAE J1113
Mechanical
Parameter
Size
Value
Comment
Including Flanges for Mounting
3.50” x 4.20” x 2.03”
(88.9mm x 106.7mm x 51.6mm)
13 oz. (368.5 g)
Weight
Revision 1.0
Page 9
RIM100 User's Manual
Environmental
Parameter
Value
IEC 60945 Classification
Degree of Protection
Operating Temperature
Storage Temperature
Relative Humidity
Vibration
Exposed
IP64
-25°C to 55°C
-40°C to 70°C
93%RH @40° per IEC60945-8.2
2-13.2Hz @ ±1mm, 13.2-100Hz @ 7m/s2 per IEC 60945-8.7
Ultraviolet B, A, Visible, and Infrared per IEC 60945-8.10
Solar Radiation
Corrosion (Salt Mist)
4 times 7days @ 40°C, 95%RH after 2 hour Salt Spray Per IEC 60945-8.12
Conducted and Radiated Emission per IEC 60945-9
Conducted, Radiated, Supply, and ESD per IEC 60945-10
Dangerous Voltage, Electromagnetic Radio Frequency per IEC 60945-12
Electromagnetic Emission
Electromagnetic Immunity
Safety Precautions
6 Technical Support
If you require technical support for Maretron products, you can reach us in any of the following
ways:
Telephone: 1-866-550-9100
Fax: 1-602-861-1777
E-mail: [email protected]
Mail: Maretron, LLC
Attn: Technical Support
9014 N. 23rd Ave Suite 10
Phoenix, AZ 85021 USA
Page 10
Revision 1.0
RIM100 User's Manual
8 Maretron (2 Year) Limited Warranty
Maretron warrants the RIM100 to be free from defects in materials and workmanship for two (2) years from the
date of original purchase. If within the applicable period any such products shall be proved to Maretron’s
satisfaction to fail to meet the above limited warranty, such products shall be repaired or replaced at Maretron’s
option. Purchaser's exclusive remedy and Maretron’s sole obligation hereunder, provided product is returned
pursuant to the return requirements below, shall be limited to the repair or replacement, at Maretron’s option, of
any product not meeting the above limited warranty and which is returned to Maretron; or if Maretron is unable to
deliver a replacement that is free from defects in materials or workmanship, Purchaser’s payment for such
product will be refunded. Maretron assumes no liability whatsoever for expenses of removing any defective
product or part or for installing the repaired product or part or a replacement therefore or for any loss or damage
to equipment in connection with which Maretron’s products or parts shall be used. With respect to products not
manufactured by Maretron, Maretron’s warranty obligation shall in all respects conform to and be limited to the
warranty actually extended to Maretron by its supplier. The foregoing warranties shall not apply with respect to
products subjected to negligence, misuse, misapplication, accident, damages by circumstances beyond
Maretron’s control, to improper installation, operation, maintenance, or storage, or to other than normal use or
service.
THE FOREGOING WARRANTIES ARE EXPRESSLY IN LIEU OF AND EXCLUDES ALL OTHER EXPRESS OR
IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND OF FITNESS FOR A PARTICULAR PURPOSE.
Statements made by any person, including representatives of Maretron, which are inconsistent or in conflict with
the terms of this Limited Warranty, shall not be binding upon Maretron unless reduced to writing and approved by
an officer of Maretron.
IN NO CASE WILL MARETRON BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, DAMAGES
FOR LOSS OF USE, LOSS OF ANTICIPATED PROFITS OR SAVINGS, OR ANY OTHER LOSS INCURRED
BECAUSE OF INTERRUPTION OF SERVICE. IN NO EVENT SHALL MARETRON’S AGGREGATE LIABILITY
EXCEED THE PURCHASE PRICE OF THE PRODUCT(S) INVOLVED. MARETRON SHALL NOT BE SUBJECT
TO ANY OTHER OBLIGATIONS OR LIABILITIES, WHETHER ARISING OUT OF BREACH OF CONTRACT OR
WARRANTY, TORT (INCLUDING NEGLIGENCE), OR OTHER THEORIES OF LAW WITH RESPECT TO
PRODUCTS SOLD OR SERVICES RENDERED BY MARETRON, OR ANY UNDERTAKINGS, ACTS OR
OMISSIONS RELATING THERETO.
Maretron does not warrant that the functions contained in any software programs or products will meet
purchaser’s requirements or that the operation of the software programs or products will be uninterrupted or error
free. Purchaser assumes responsibility for the selection of the software programs or products to achieve the
intended results, and for the installation, use and results obtained from said programs or products. No
specifications, samples, descriptions, or illustrations provided Maretron to Purchaser, whether directly, in trade
literature, brochures or other documentation shall be construed as warranties of any kind, and any failure to conform
with such specifications, samples, descriptions, or illustrations shall not constitute any breach of Maretron’s limited
warranty.
Warranty Return Procedure:
To apply for warranty claims, contact Maretron or one of its dealers to describe the problem and determine the
appropriate course of action. If a return is necessary, place the product in its original packaging together with
proof of purchase and send to an Authorized Maretron Service Location. You are responsible for all shipping and
insurance charges. Maretron will return the replaced or repaired product with all shipping and handling prepaid
except for requests requiring expedited shipping (i.e. overnight shipments). Failure to follow this warranty return
procedure could result in the product’s warranty becoming null and void.
Maretron reserves the right to modify or replace, at its sole discretion, without prior notification, the warranty listed
above. To obtain a copy of the then current warranty policy, please go to the following web page:
Page 12
Revision 1.0
®
Appendix A – NMEA 2000® Interfacing
RIM100 NMEA 2000® Periodic Data Transmitted PGNs
PGN 127501 – Binary Switch Bank Status
The RIM100 uses this PGN to transmit the state of each of the connected switch inputs
Field 1: Indicator Bank Instance – This field identifies the particular switch bank to which this
value of this field.
2: Indicator #1 – This field indicates the state of the switch connected to the V1+ and
V1- inputs of the RIM100. The state will be one of the following values:
• “Off” – No voltage is detected on the monitored load (the load is not running).
• “On” – A voltage is detected on the monitored load (the load is running).
• “Data Not Available” – The indicator is configured as “Disabled”
3: Indicator #2 – This field indicates the state of the switch connected to the V2+ and
V2- inputs of the RIM100.
4: Indicator #3 – This field indicates the state of the switch connected to the V3+ and
V3- inputs of the RIM100.
5: Indicator #4 – This field indicates the state of the switch connected to the V4+ and
V4- inputs of the RIM100.
6: Indicator #5 – This field indicates the state of the switch connected to the V5+ and
V5- inputs of the RIM100.
7: Indicator #6 – This field indicates the state of the switch connected to the V6+ and
V6- inputs of the RIM100.
Revision 1.0
Appendix A – NMEA 2000 Interfacing
Page A1
|