Lochinvar Water Heater 0502 1302 User Manual

PUMP  
Recommendation  
PUMP-Rec-16 Rev C  
PUMP RECOMMENDATION FOR  
POWER-FIN 0502-1302 WATER HEATER  
Pump Specifications  
Part No.  
HorsePower  
Flanges  
Valute Material  
Flange Material  
Vendor  
Vendor Product Series  
Orientation  
PUM3013  
2/5  
2"  
Brass  
Brass  
Armstrong  
E Series  
Horizontal  
Installation Specifications  
Recommended for  
Model Numbers  
Power-fin, PF(N,L) 0502-1302  
Based on  
Based on  
Installation Type  
Single Water Heater piped to Single Storage Tank  
Pump  
Maximum GPM  
75 GPM  
Based on  
Connecting piping  
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee  
PUM3013  
Minimum Pipe Diameter  
2-1/2"  
IMPORTANT: Read the Power-fin 0502-2001 Installation and Operation Manual. If the planned system exceeds  
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.  