FC600/TMAX/78
• Addressable conventional technology
• Individual detector identification with
optional address module
• Alarm temperature 78°C
• Allows for connection of external
remote indicator
• Anti-tamper locking feature on
detector base
• Function check by means of test
magnet
Description
The Thermal Max Detector FC600/TMAX/78 recogni-
ses a temperature of 78°C as alarm threshold and is
compliant to EN 54-5 (class BS) standards. It can be
used in rooms with a height of up to 6m. Any alarm
will be transmitted to the fire detection panel in con-
ventional technology. An individual detector identifica-
tion can be obtained with the optional Address Module
NG58-1.
easy identification of the alarming detector. In addition,
a remote indicator can also be connected.
Several types of detector bases are available to faci-
litate quick and easy installation. To prevent unautho-
rized removal of the detector, all detector bases are
equipped with an anti-tamper locking feature. A de-
tector function test can be conveniently conducted by
using a test magnet.
The detector is equipped with an LED indicator which
is visible from all sides at any angle and thus facilitates
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × h (without base)
Colour
10 – 30VDC (supply through detector line voltage)
typ. 40µA (normal condition)
78°C
max. +60°C
-30°C to +70°C (continuous operation)
max. 95% (no condensation)
106 × 46 (mm)
white
Weight
80g
Approvals
LPCB 603b/01
0832-CPD-0126
Order number
Order name
242071
Thermal Max Detector/Conv./FC600 FC600/TMAX/78
0832–CPD–0126
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
FC600-TMAX-78_DBL_LST_EN_0850.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
|