Siren Connection Module  
SZ58-3  
• Four independent, individually fused  
siren outputs  
• 500mA load current per output  
• Monitoring of the siren circuits  
• LEDs indicate activation and faults of  
siren circuits  
• Activation by means of actuation  
outputs or external switches  
Description  
The Siren Connection Module SZ58-3 is installed in Fire  
Detection Control Panels Series BC216, BC016 and  
BC06 for connecting acoustical or optical signalling  
devices (e.g., sirens) to four independently actuatable  
circuits with line monitoring. The siren circuits are indi-  
vidually protected by means of self-healing electronic  
fuses. The activation of the siren circuits is carried  
out by the control panel or manually by means of swit-  
ches.  
creased current demand, through an external power  
supply. The supply of the siren circuits is automatically  
monitored for undervoltages.  
The componentry is equipped with four fault detection  
outputs which report the fault condition of power supp-  
ly and siren lines to the control panel.  
For each output there are separate LEDs for indication  
of fault and activation.  
The signalling devices can be supplied either directly  
by the fire detection control panel, or, in case of in-  
The siren connection module is mounted on a bracket  
inside the housing of the fire detection control panel.  
Specifications  
Operating voltage  
21 – 30VDC  
External supply voltage for signalling devices  
Current consumption at 24V  
Load current per output  
Output voltage, siren circuit quiescent  
Output voltage, siren circuit active  
End-of-line resistor  
21 – 30VDC  
15mA (quiescent, outputs terminated)  
max. 500mA  
-1.2VDC  
external supply voltage minus approx. 1V  
5.6kΩ  
Surveillance current, quiescent state  
Ambient temperature  
typ. 240µA  
-5°C to +50°C  
max. 95% (no condensation)  
98 × 74 × 18 (mm)  
60g  
Relative humidity  
Dimensions L × W × H  
Weight  
Order number  
223026  
Order name  
Siren Connection Module SZ58-3  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
SZ58-3_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

Lenovo Laptop 3000H User Manual
LG Electronics Cell Phone 4600 User Manual
LG Electronics Clothes Dryer DLE1001W User Manual
Lightolier Indoor Furnishings 1004ICXN User Manual
Lucent Technologies Telephone 362EC User Manual
Makita Saw Model 5007NL User Manual
Martin Audio Portable Speaker W8LCDI User Manual
Mercury Automobile Parts D73L D TRONIC User Manual
Mesa Boogie Stereo Amplifier 290 User Manual
Micro Innovations Speaker MM635F User Manual