LG Electronics Server PCS100R User Manual

PCS100R Pro:Centric™  
Server  
Installation & Setup Guide  
Warranty  
© Copyright 2011, LG Electronics U.S.A., Inc.  
P/N: 206-4142 (Rev D)  
 
IMPORTANT SAFETY INSTRUCTIONS  
1. Read these instructions.  
2. Keep these instructions.  
3. Heed all warnings.  
14. Power Sources  
This product should be operated only from the  
type of power source indicated on the marking  
label. If you are not sure of the type of power  
supply to your INSTALLATION, consult your  
product dealer or local power company.  
4. Follow all instructions.  
5. Do not use this apparatus near water.  
6. Clean only with dry cloth.  
15. Overloading  
7. Do not block any ventilation openings.  
Install in accordance with the manufac-  
turer's instructions.  
Do not overload wall power outlets and  
extension cords as this can result in a risk of  
fire or electric shock.  
8. Do not install near any heat sources,  
such as radiators, heat registers, stoves,  
or other apparatus (including amplifiers)  
that produce heat.  
16. Disconnect Device  
The AC mains plug is used as the disconnect  
device. The disconnect device must remain  
readily operable.  
9. Do not defeat the safety purpose of the  
polarized or grounding-type plug. A polar-  
ized plug has two blades with one wider  
than the other. A grounding-type plug has  
two blades and a third grounding prong.  
The wide blade or the third prong are pro-  
vided for your safety. If the provided plug  
does not fit into your outlet, consult an  
electrician for replacement of the obsolete  
outlet.  
17. Object and Liquid Entry  
Never push objects of any kind into this prod-  
uct through openings as they may touch dan-  
gerous voltage points or short-out parts that  
could result in a fire or electric shock. Never  
spill liquid of any kind on the product. Do not  
use liquid cleaners or aerosol cleaners.  
18. Outdoor Use  
Warning: To prevent fire or shock  
hazards, do not expose this product  
to rain or moisture.  
10. Protect the power cord from being walked  
on or pinched, particularly at plugs,  
convenience receptacles, and the point  
where it exits from the apparatus.  
19. Wet Location  
Do not use this product near water or mois-  
ture or in an area, such as a basement, that  
might become flooded. The apparatus shall  
not be exposed to dripping or splashing and  
no objects filled with liquids, such as vases,  
shall be placed on the apparatus.  
11. Only use attachments/accessories speci-  
fied by the manufacturer.  
12. Use only with the cart, stand, tripod,  
bracket, or table specified by the manu-  
facturer or sold with the apparatus. When  
a cart is used, use caution when moving  
the cart/apparatus combination in order  
to avoid injury from tip-over.  
20. Test Equipment  
In some cases, LG has supplied or recom-  
mended the use of test equipment and devic-  
es for the setup and testing of the equipment.  
The operation and maintenance of test equip-  
ment is described in their associated instruc-  
tion manuals. Please refer to these manuals  
for explicit instructions regarding the safe use  
and handling of the equipment.  
13. Refer all servicing to qualified service  
personnel. Servicing is required when the  
apparatus has been damaged in any way,  
such as power-supply cord or plug is  
damaged, liquid has been spilled or  
objects have fallen into the apparatus, the  
apparatus has been exposed to rain or  
moisture, does not operate normally, or  
has been dropped.  
(Continued on next page)  
3
206-4142  
 
 
IMPORTANT SAFETY INSTRUCTIONS  
(Continued from previous page)  
24. Safety Check  
Upon completion of any service or repairs to  
this product, ask the service technician to  
perform safety checks to determine that the  
product is in proper operating condition.  
21. Damage Requiring Service  
Unplug this product from the wall power out-  
let and refer servicing to qualified service  
personnel under the following conditions:  
PCS100R Rack Installation (also see pages 9  
a. If the power-supply cord or plug is damaged.  
and 10)  
b. If liquid has been spilled, or objects have  
fallen into the product.  
To install the PCS100R in a rack:  
c. If the product has been exposed to rain or  
water.  
• Carefully slide the PCS100R into a standard  
19-inch equipment rack.  
d. If the product does not operate normally  
by following the operating instructions.  
Adjust only those controls that are covered  
by the operating instructions, as an  
• When mounted in the rack, make sure appro-  
priate hardware is used. ALL FOUR MOUNT-  
ING SCREWS MUST BE USED.  
• This equipment is not designed to support  
other devices. Do NOT stack other equipment  
on the top of the PCS100R.  
improper adjustment of other controls may  
result in damage and will often require  
extensive work by a qualified technician to  
restore the product to its normal operation.  
• Rear cabling must be dressed and supported  
so that the weight of the cabling is not a strain  
on the PCS100R connectors.  
e. If the product has been dropped or the  
cabinet has been damaged.  
• MOUNTING OF THE EQUIPMENT IN THE  
RACK SHOULD BE SUCH THAT A HAZARD-  
OUS CONDITION IS NOT ACHIEVED DUE TO  
UNEVEN MECHANICAL LOADING.  
f. If the product exhibits a distinct change in  
performance.  
Caution: Refer all servicing to qualified  
service personnel.  
Rack-mount Considerations  
22. Servicing  
A. Elevated Operating Ambient  
Caution: These servicing instruc-  
tions are for use by qualified service  
personnel only. To reduce the risk  
of electrical shock, do not perform any  
servicing other than that described in the  
operating instructions unless you are  
qualified to do so.  
If installed in a closed or multi-unit rack  
assembly, the operating ambient tempera-  
ture of the rack environment may be greater  
than room ambient. Therefore, consideration  
should be given to installing the equipment in  
an environment compatible with the maximum  
ambient temperature (Tma) specified by the  
manufacturer (see “Specifications” information  
in this document).  
23. Replacement Parts  
When replacement parts are required, be  
sure the service technician uses replacement  
parts specified by the manufacturer or that  
have the same characteristics as the original  
parts. Unauthorized substitutions may result  
in fire, electric shock, or other hazards.  
B. Reduced Air Flow  
Installation of the equipment in a rack should  
be such that the amount of air flow required  
for safe operation of the equipment is not  
compromised. Do NOT stack other equipment  
on the top of the PCS100R unit.  
(Continued on next page)  
206-4142  
4
 
IMPORTANT SAFETY INSTRUCTIONS  
(Continued from previous page)  
PCS100R Installation on a Flat Surface  
To install the PCS100R on a level surface (table  
top, shelf, stacked with other equipment, etc.):  
C. Circuit Overloading  
Consideration should be given to the con-  
nection of the equipment to the supply circuit  
and the effect that overloading of the circuits  
might have on overcurrent protection and  
supply wiring.  
• Carefully place the PCS100R on a level surface.  
• Note the operating temperature from the speci-  
fications.  
• Do NOT stack other equipment on the top of  
the PCS100R.  
D. Reliable Earthing  
Maintain reliable earthing of rack-mounted  
equipment. Particular attention should be  
given to supply connections other than direct  
connections to the branch circuit (e.g. use of  
power strips).  
• If necessary, place spacers or rubber feet (not  
provided) on top and bottom.  
E. Mains Outlet Earthing  
The apparatus with Class I construction must  
be connected to a mains socket outlet with a  
protective earthing connection.  
5
206-4142  
 
 
Table of Contents / Setup Checklist  
Table of Contents  
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . 2  
Important Safety Instructions. . . . . . . . . . . . 3 5  
Table of Contents / Setup Checklist . . . . . . . . 6  
PCS100R Product Description . . . . . . . . . . . . 7  
Rear and Front Panel Overviews . . . . . . . . . . 8  
Rack Installation . . . . . . . . . . . . . . . . . . . . 9 10  
System Setup . . . . . . . . . . . . . . . . . . . . . 11 12  
Troubleshooting / Specifications . . . . . . . . . . 13  
Document Revision History / Notes . . . . . . . 14  
Open Source Software Notice. . . . . . . . . . . . 15  
Warranty . . . . . . . . . . . . . . . . . . . . . Back Cover  
Setup Checklist  
1. Unpack the PCS100R Pro:Centric™ server unit and all accessories.  
Accessories provided: Power Cord and Adapter  
2. Select the location for mounting the PCS100R. Ensure that there is adequate ventilation  
available  
.
3. Obtain the necessary attachment hardware to mount the PCS100R chassis in its targeted  
location.  
4. Plan and install the necessary cabling and network (Ethernet) and AC power access for the  
PCS100R. You will also need the following to connect a PC directly to the PCS100R for system  
setup verification purposes:  
• DB9 Male-to-DB9 Female RS-232 straight-through serial cable (Example: Cables Unlimited  
PCM-2100-06 serial cable)  
• (Optional) USB 2.0-to-serial DB9 adapter (Example: Cables Unlimited USB-2920 adapter). If  
there is no serial port on the PC, use the adapter to connect the serial cable to the PC.  
5. Carefully follow the rack installation procedure for the PCS100R (see pages 9 and 10).  
6. If not already done, install the modulator and upconverter that will receive the ASI output signal  
from the PCS100R. Refer to the manufacturer’s documentation.  
7. Complete the setup procedure for the PCS100R (see pages 11 and 12).  
6
206-4142  
 
 
PCS100R Product Description  
The PCS100R Pro:Centric server is a stand-alone, remotely-controlled processor/  
controller for the Pro:Centric system. This device can be used to capture data from  
an Internet source, assemble the data as display pages, and output the pages in  
DTV format over the ASI. With appropriate post-processing, this ASI signal can  
then be used for either IP or RF distribution in a lodging site application.  
Features  
Remote programming capability via Ethernet  
Unit does not require local monitor, keyboard, or mouse connection  
Small, lightweight chassis  
19-inch rack-mountable  
1U height profile to minimize rack-space usage  
Note: Design and specifications subject to change without prior notice.  
7
206-4142  
 
 
Rear and Front Panel Overviews  
PCS100R  
Rear View  
POWER  
12V 5A  
/
RS  
-232  
.
.
.
.
.
.
.
.
.
ASI-  
OUT  
RS-232  
Port  
M
A
C
ADDRESS:  
00:0C:63:33:00:0`1  
NE  
T
WORK  
Power  
Supply/Cord  
ASI Out  
SOFT  
RESE  
W
ARE  
T
NETWORK  
(Ethernet)  
Port  
Disconnect Device  
The AC mains plug is used as the  
disconnect device. The disconnect  
device must remain readily operable.  
SOFTWARE  
RESET Button  
PCS100R  
Front View  
S
T
A
T
U
S
STATUS LED  
8
206-4142  
 
 
Rack Installation  
Installing the PCS100R in a Rack  
1. Carefully slide the chassis into a standard 19-inch equipment rack.  
2. Use all four mounting screws to secure the chassis to the rack (see diagram below).  
3. Refer to “Surge Protected Power Strip Requirements” below. Although power is not actually  
applied to the PCS100R until later during the system setup (see “Typical System Installation”  
on page 12), the power strip should be readied at this time.  
S
T
A
T
U
S
Surge Protected Power Strip Requirements  
(see also diagram on following page)  
• The PCS100R AC line should be plugged in to the surge protected power strip.  
• Any modulators, upconverters, accessories, etc. connected to the ASI output of the PCS100R  
also should be connected to this same surge protected power strip.  
• The power strip should provide surge protection in both Normal (hot to neutral) and Common  
(hot to ground and neutral to ground) Modes.  
• The surge suppression should be 600 joules minimum, though 3800 joules is preferred, with  
UL1499 rated let-through voltage equal to 330 volts.  
The surge protected power strip should conform to the ANSI C62.41 standard or equivalent.  
9
206-4142  
 
 
Rack Installation (Cont.)  
PCS100R  
ASI OUT  
PCS100R  
Power Connector  
POWER  
NETWORK  
ASI-OUT  
12V  
/
5A  
RS-232  
SOFTWARE  
RESET  
.....  
....  
PCS100R  
AC IN  
ASI IN  
To AC  
power  
source  
Typical modulator/  
upconverter unit  
75 ohm  
BNC-to-BNC  
coaxial cable  
Modulator/Upconverter  
Power Supply/Cord  
Modulator  
ASI IN  
PCS100R Power  
Supply/Cord  
Surge Protected  
Power Strip  
Disconnect Device  
The AC mains plug is used as the disconnect device.  
The disconnect device must remain readily operable.  
Rack-mount Considerations  
C. Circuit Overloading  
A. Elevated Operating Ambient  
Consideration should be given to the con-  
nection of the equipment to the supply circuit  
and the effect that overloading of the circuits  
might have on overcurrent protection and  
supply wiring.  
If installed in a closed or multi-unit rack  
assembly, the operating ambient tempera-  
ture of the rack environment may be greater  
than room ambient. Therefore, consideration  
should be given to installing the equipment  
in an environment compatible with the maxi-  
mum ambient temperature (Tma) specified by  
the manufacturer (see “Specifications” infor-  
mation in this document).  
D. Reliable Earthing  
Maintain reliable earthing of rack-mounted  
equipment. Particular attention should be  
given to supply connections other than direct  
connections to the branch circuit (e.g. use of  
power strips).  
B. Reduced Air Flow  
Installation of the equipment in a rack should  
be such that the amount of air flow required  
for safe operation of the equipment is not  
compromised. Do NOT stack other equipment  
on the top of the PCS100R unit.  
E. Mains Outlet Earthing  
The apparatus with Class I construction must  
be connected to a mains socket outlet with a  
protective earthing connection.  
10  
206-4142  
 
 
System Setup  
Refer to the following diagrams, and complete the system installation as described on page 12.  
Typical Setup Flow Chart for the PCS100R  
R
RF  
oom  
Network  
R
R
R
ec  
eiv  
er  
Distribution  
System  
PCS100R  
ASI Out  
R
oom  
ec  
eiv  
er  
Combiner  
ASI In  
QAM  
Modulator  
IF Out  
IF In  
ASI  
Coaxial  
Cable  
RF  
DTV  
Coaxial  
Cable  
RF  
Cable  
R
Upconverter  
oom  
ec  
eiv  
er  
RF Out  
VPN Network Connections Overview  
Pro:Centric  
VPN Server  
VPN Client  
Internet/  
VPN  
PCS100R  
Laptop  
PC  
VPN Client  
11  
206-4142  
 
 
System Setup (Cont.)  
Typical System Installation  
(see also Typical Setup Flow Chart and VPN Network Connections Overview on page 11)  
1. Connect a 75 ohm BNC-to-BNC coaxial cable between ASI OUT on the PCS100R and ASI IN  
on the modulator.  
Note: The BNC cable must be less than 30 feet (9.2 meters) in length.  
2. Connect an RF coaxial cable between IF OUT on the modulator and IF IN on the upconverter.  
3. Connect one end of a CAT5 RJ-45 Ethernet cable to the NETWORK port on the PCS100R  
rear panel, and connect the other end of the cable to the institution’s network.  
4. Connect the PCS100R power supply to the POWER connector on the PCS100R rear panel.  
5. Use the straight-through serial cable and, if necessary, the USB adapter to connect a PC to  
the RS-232 port on the PCS100R rear panel. (This step will enable you to verify the network  
connection once power is applied in step 7.)  
6. Using HyperTerminal or an equivalent terminal emulation program on the PC, configure the  
serial port as follows: Bits per second = 115200; Data bits = 8; Parity = None; Stop bits = 1;  
Flow Control = None  
7. Plug the PCS100R AC power cord into the surge protected power strip (see “Surge Protected  
Power Strip Requirements” on page 9). When power is applied, the STATUS LED on the  
PCS100R front panel will light, and you will see boot-up messages on the PC.  
When the boot-up is complete, a System Information display identifies important information  
about the PCS100R, including the unit serial number, hardware ID (firmware version), software  
versions, MAC address, and IP address, for example:  
PCS100R Pro:Centric Server v3.3  
SN:  
001-12090025  
Hardware ID: 0.0.0.15  
OS version: Linux 2.6.33-zenith-pcs100r  
OS release: #98 Mon Aug 9 09:36:05 CDT 2010  
MAC Address: 00:0C:63:3B:00:0E  
IP Address: 192.168.0.51  
Datarate:  
high (38.8 Mbps)  
Local time: Thu Jan 13 12:50:32 EDT 2011  
8. Check the IP Address field in the display. By default, the PCS100R uses DHCP; thus, the DHCP  
server assigns an IP address to the PCS100R once the PCS100R successfully connects to the  
network. If the IP Address field shows an IP address, the PCS100R is up and running on the net-  
work. If the IP Address field is blank, refer to Troubleshooting information on the following page.  
9. Connect the RF output on the upconverter to the RF distribution center combiner, and  
balance the RF signal so that the signal level at the TV(s) is between 0 to +7 dBmV.  
Caution: For proper system performance, the Pro:Centric signal level at the  
TV input (ANTENNA IN) must be between 0 to +7 dBmV. Note that additional  
equipment may be required to adjust the signal level.  
12  
206-4142  
 
 
Troubleshooting / Specifications  
Troubleshooting  
If the PCS100R is not connecting to the network, i.e., the IP Address field in the System  
Information display (see setup procedure on previous page) is blank:  
1. Check the NETWORK connector on the rear panel of the PCS100R. Make sure the cable  
connection is tight and secure.  
2. Observe the green LED on the NETWORK port. Once the PCS100R is connected to the  
network, the LED will be lit continuously.  
3. Contact the network administrator to verify the network status.  
Specifications  
Dimensions  
Height:  
Width:  
Depth:  
Weight:  
1.692 inches (42.977 mm)  
19.0 inches (482.6 mm) (for EIA standard 19-inch rack mount)  
8.5 inches (215.9 mm)  
2.70 pounds (1.22 kgrms) rack-only weight  
Environmental Storage Conditions  
Temperature:  
-20° to 70° Celsius  
-4° to 158° Fahrenheit  
95% non-condensing  
Humidity:  
Environmental Operating Conditions  
Temperature (Tma): 0° to 35° Celsius  
32° to 95° Fahrenheit  
Humidity:  
95% non-condensing  
Electrical  
DC Input:  
+12V DC @ 5 Amps  
75 ohms  
800 mv  
Impedance at ASI Out jack:  
Level at ASI Out jack:  
Ethernet:  
10/100/1000BaseT  
Note: Design and specifications subject to change without prior notice.  
13  
206-4142  
 
 
Document Revision History / Notes  
Document Revision History  
Date  
Description  
June 2010  
Revision A: New document  
September 2010  
January 2011  
November 2011  
Revision B: Specifications update  
Revision C: System setup update  
Revision D: Surge protected power strip requirements added  
Product documentation is available online at: www.LGsolutions.com/products. From the Products  
page, select TVs, Systems & Solutions, then Head End Systems, then Pro:Centric Server (click  
Show [+] to view the list of products), then PCS100R. Click the Literature & Downloads tab at the  
bottom of the PCS100R page, and select the required document(s) from the Downloads list.  
Notes  
14  
206-4142  
 
 
Open Source Software Notice  
The following GPL executables and LGPL libraries used in this  
product are subject to the GPL Version 2.0/LGPL Version 2.1  
License Agreements:  
Copyright © 2001, 2003 Jakob Schlyter  
Copyright © 1996 Jason Downs  
Copyright © 2002 Juha Yrjölä  
Copyright © 2000 Michael Stone  
GPL EXECUTABLES: Linux kernel 2.6.33, LTIB 10.1.1,  
bash-2.05b, busybox-1.1.3, e2fsprogs-1.34, ethtool-3, gawk-  
3.1.3, lrzsz_0.12.21, lzo-2.03, mtd-utils-1.2.0, net-tools-1.60,  
ntpclient_2003_194, openvpn-2.1.1, pciutils-2.1.11, ppp-2.4.1,  
procps-3.1.11, screen-4.0.2-1, skell-1.13, time-1.7  
Copyright © 2002 Networks Associates Technology, Inc.  
Copyright © 1997, 1998, 2000-2002, 2004 Todd C. Miller  
Copyright © 2003, 2004, 2005 Darren Tucker  
Copyright © 1988-2002 Sun Microsystems, Inc.  
Copyright © 2005 The SCO Group  
LGPL LIBRARIES: eglibc 2.8, libelf-0.8.5, termcap-2.0.8  
Copyright © 2004 The OpenBSD Project  
Copyright © 2005 Anil Madhavapeddy  
Copyright © 1994 Phil Karn  
Copyright © 1996-1998, 2003 William Allen Simpson  
Copyright © 2003 Peter Stuge  
To obtain the source code under GPL, LGPL, MPL and other  
open source licenses that are contained in this product, please  
all referenced license terms, warranty disclaimers and copy-  
right notices are available for download. LG Electronics  
will also provide open source code to you on CD-ROM for a  
charge covering the cost of performing such distribution (such  
as the cost of media, shipping and handling) upon e-mail  
request to [email protected]. This offer is valid for three (3)  
years from the date on which you purchased the product.  
Copyright © 2005 Reyk Floeter  
Copyright © 1991 Massachusetts Institute of Technology  
Copyright © 2004 Ted Unangst and Todd Miller  
Copyright © 1999 WIDE Project  
Copyright © 1996 Internet Software Consortium  
Portions Copyright © 1999-2001 Internet Software Consor-  
tium  
You can obtain a copy of the GPL, LGPL licenses from: http://  
Portions Copyright © 1993 Digital Entertainment Corpora-  
tion  
Portions Copyright © 1995 International Business Ma-  
chines, Inc.  
• OpenSSL-1.0.0:  
Copyright © 1998-2008 The OpenSSL Project  
Copyright © 1995-1998 Eric Young  
This product includes:  
• OpenSSH-4.3p2:  
Copyright © 1994, 1995 Tatu Ylonen, Espoo, Finland  
Copyright © 1998 CORE SDI S.A., Buenos Aires, Argen-  
tina  
All rights reserved.  
Copyright © 1995, 1996 by David Mazieres  
Copyright © 1980, 1983, 1987, 1988, 1990, 1992, 1993,  
1995 The Regents of the University of California  
Copyright © 1999, 2000, 2001, 2002, 2003, 2004 Markus  
Friedl  
Copyright © 1995, 1996, 1998, 1999 Theo de Raadt  
Copyright © 1999, 2000, 2001, 2002 Niels Provos  
Copyright © 1999 Dug Song  
Permission is hereby granted, free of charge, to any person  
obtaining a copy of this software and associated documen-  
tation files (the “Software”), to deal in the Software without  
restriction, including without limitation the rights to use, copy,  
modify, merge, publish, distribute, sublicense, and/or sell cop-  
ies of the Software, and to permit persons to whom the Soft-  
ware is furnished to do so, subject to the following conditions:  
Copyright © 1999 Aaron Campbell  
Copyright © 1999, 2000, 2001, 2002, 2003, 2004, 2005  
Damien Miller  
Copyright © 2001 Kevin Steves  
Copyright © 2002 Daniel Kouril  
SUBJECT TO THE TERMS OF THE GPL VERSION 2.0/LGPL  
VERSION 2.1 LICENSE AGREEMENTS, THE SOFTWARE IS  
PROVIDED “AS IS”, WITHOUT WARRANTY OF ANY KIND,  
EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO  
THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR  
A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN  
NO EVENT SHALL THE AUTHORS, COPYRIGHT HOLDERS,  
OR LG ELECTRONICS (THE “LICENSOR”) BE LIABLE FOR  
ANY CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER  
IN AN ACTION OF CONTRACT, TORT OR OTHERWISE,  
ARISING FROM, OUT OF OR IN CONNECTION WITH THE  
SOFTWARE OR THE USE OR OTHER DEALINGS IN THE  
SOFTWARE, EVEN IF LICENSOR HAS BEEN ADVISED  
OF THE POSSIBILITY OF SUCH DAMAGES. LICENSEE  
ASSUMES THE COST OF ALL NECESSARY SERVICING,  
REPAIR, OR CORRECTION.  
Copyright © 2003 Wesley Griffin  
Copyright © 2001 Per Allansson  
Copyright © 2002, 2003 Nils Nordman  
Copyright © 2001-2003 Simon Wilkinson  
Copyright © 2000, 2001 2003 Ben Lindstrom  
Copyright © 2002, 2005 Tim Rice  
Copyright © 2000 Andre Lucas  
Copyright © 2002 Chris Adams  
Copyright © 2000, 2001 Corinna Vinschen  
Copyright © 2002 Cray Inc. (Wendy Palm)  
Copyright © 2000 Denis Parker  
Copyright © 2001 Gert Doering  
15  
206-4142  
 
 
LG PCS100R Pro:Centric Server Warranty  
Broadcast Products  
Welcome to the LG family! We believe that you will be pleased with your new PCS100R Pro:Centric Server. Please read  
this warranty carefully, it is a “LIMITED WARRANTY” as defined under Federal Law. This warranty gives you specific legal  
rights, and you may also have other rights that vary from state-to-state within the U.S.A.  
LG’s RESPONSIBILITY  
Warranty Term  
Parts  
One year parts and labor from date of purchase or delivery date.  
New or remanufactured replacements for factory-defective parts may be used. Such replacement parts are warranted for  
the remaining portion of the original warranty period.  
Warranty Service  
Not Covered  
Warranty service is provided at LG. Customer pays for shipping charges to LG; LG pays for return shipping charges to  
return PCS100R Pro:Centric Server to customer. Call 1-888-865-3026 for further information.  
This warranty covers manufacturing defects and does not cover installation, adjustment of customer controls, installation  
or repair of antenna systems, cable converters or cable company-supplied equipment; it also does not cover damage due  
to misuse, abuse, negligence, acts of God or other causes beyond the control of LG. Any alteration of the product after  
manufacture voids this warranty in its entirety.  
THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTY, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION,  
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND LG SHALL NOT BE  
LIABLE FOR ANY CONSEQUENTIAL, INDIRECT, OR INCIDENTAL DAMAGES OF ANY KIND, INCLUDING LOST  
REVENUES OR PROFITS IN CONNECTION WITH THIS PRODUCT. SOME STATES DO NOT ALLOW LIMITATIONS  
ON HOW LONG AN IMPLIED WARRANTY LASTS OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR  
CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU.  
OWNER’S RESPONSIBILITY  
Effective Warranty Date Warranty begins on the date of delivery of the PCS100R Pro:Centric Server.  
For your convenience, keep the dealer’s dated bill of sale or delivery ticket as evidence of the purchase date.  
Installation Guide  
Warranty Service  
Read the Installation & Setup Guide carefully so that you will understand the operation of the PCS100R Pro:Centric Server  
and how to adjust the settings.  
For warranty service information, call 1-888-865-3026. Parts and service labor that are LG’s responsibility (see above)  
will be provided without charge. Other service is at the owner’s expense. If you have any problem in obtaining satisfactory  
warranty service, call 1-888-865-3026.  
You must provide the model number, serial number and date of purchase or date of original installation.  
For Customer Support/Service, please call:  
1-888-865-3026  
Pro:Centric is a trademark of LG Electronics U.S.A., Inc. All other trademarks or  
registered trademarks are the property of their respective owners.  
206-4142  
Revision D  
Copyright 2011, LG Electronics U.S.A., Inc.  
 
 

La Crosse Technology Universal Remote RS 204U CS User Manual
Land Pride Lawn Mower AFM4214 User Manual
Lasko Gas Heater 2084537 User Manual
Lennox International Inc Air Cleaner CBX40UHV User Manual
Lochinvar Water Heater CB986 2066 User Manual
LST Smoke Alarm ND2251EM User Manual
Luxeon Projector D315M User Manual
Makita Saw 2414NB User Manual
Manitowoc Ice Refrigerator 14514 2 08 User Manual
Midland Radio Two Way Radio GXT500 GXT550 GXT565 User Manual